CIR-eQ User’s Manual

Primary voltage*: When using transformers to measure the voltage, enter the primary

voltage value of the transformer. The information related to this feature of the

transformer can be found on a features label on the transformer. This label must

indicate the primary ratio. In case you are not using voltage transformers and you are

taking a direct measurement (up to 400 V ph-n), the value entered must be 1.

Secondary voltage*: When using transformers to measure the voltage, enter the

secondary voltage value of the transformer. The information related to this feature of

the transformer can be found on a features label on the transformer. This label must

indicate the secondary ratio.

In case you are not using voltage transformers and you are taking a direct

measurement, the value entered must be 1.

the setup of voltage transformer relation has a limit that depends on some

conditions which are defined with the range:

1º. Primary voltage value

between 1 and 220.000

2º. Secondary voltage value

between 1 and 999

3º. Value of primary/secondary

between 1 and10.000

Nominal voltage (Ph-n): Enter the nominal voltage value between the installation's phase

and neutral between 50…400V. That value has to be equal to the secondary of the

voltage transformer if it is different to 1.

Nominal Freq.: Enter the nominal value of the installation's frequency. The values

allowed for this field are 50 or 60 Hz.

Over voltage level: The threshold for detecting an over voltage is introduced in %. Is

referenced to the value entered in the field nominal voltage. It is the value above

which the device records an event of over voltage. The margin of that set point is

between 100 and 150%

Sag level: The threshold for detecting a sag is introduced in %. Is referenced to the value

entered in the field nominal voltage. Is the value below which the device recorded a

sag event in voltage. The margin is between 1 and 20%.

Interruption level: The threshold for detecting an interruption and is introduced in %. Is

referenced to the value entered in the field nominal voltage. Is the value below which

the device recorded an interruption event in voltage. The margin is between 50 and

97%.

Over voltage hysteresis: Is the value in % to be recovered the voltage after an over

voltage (within the voltage range defined as normal) to record the end of the event.

The margin of this field is from 0 to 5 %.

Sag hysteresis: Is the value in % to be recovered the voltage after a sag voltage (within

the voltage range defined as normal) to record the end of the event. The margin of

this field is from 0 to 5 %

Interruption hysteresis: Is the value in% to be recovered the voltage after an interruption

voltage (within the voltage range defined as normal) to record the end of the event.

The margin of this field is from 0 to 5 %