6.6.- VISUALIZATION OF DATA RECORDED

CIR-eQ records two different file types. One is a STD file which includes standard

electrical parameters. The other is EVQ file that includes quality events recorded by the

analyzer. Is recommended for study the data recorded using the software Power Vision

or Power Vision +, that allow visualization of the two types of files and display data using

graphs and / or tables.

However, it is possible to send data standard (STD file) of the web of CIR-e3. To register

as a user of the Web, send and display STD data, see Chapter 8. CIR-e3 Web.

7.- QUALITY EVENTS

By way of example shows a graph of the possible evolution of a voltage signal observed

in the three event types that are registered with CIR-eQ.

The graph shows a quality event for voltage bounded in the t0 interval time. The duration

of the event of over voltage is equal to the time the signal is above the value set to detect

over-voltages (equal to 110% of Vnom) plus the time it takes the signal to fall below the

hysteresis value (About V His ) normally scheduled at 2%. Other events visible in the

graph are bounded in t1 and t3. These events correspond with some gaps. The overall

gap is set at 90% of Vnom so register until fall below 10% (in this case is recorded as

interruption, represented in the graph in the interval t2 or recovers back above 90%

configured, plus 2% hysteresis (Sag Hys).

Quality events recording the CIR-eQ must have a minimum duration of 10ms. If the event

does not last the minimum time is not recorded as such, even if it affects the average

value calculated for that period.