Page 15
9
ACCESSIBLE CONNECTIONS (Metal box controller)
Computer board:
J9
Diagnostics display plug
J10
Connection to Power supply / Relay board
J17
Mat fault and Zone fault lights plug
J11
Push-button zone reset plug (N.O.)
J12
Remote push-button zone reset plug (N.O.)
Terminal No.
Function
Usage
GND
Ground
For zone LED's
1,2,3
1,2,3
short to ground pin to reset zone in manual mode
J13
DEVICENET PLUG
Terminal No.
Usage
GND
Ground
CANH,CANL
Twisted pair data lines
J1,J2,J3,J4,J5,J6,J7,J8 Mat input terminals (1 to 8)
Terminals No.
Usage
1,2
Return from mat (1=blue, 2=white)
3,4
20vdc Output to mat (3=black, 4=brown)
NOTE: Canadian market wiring is black, red, red, black with 18-guage wiring size.
Power Supply Board:
J3
Power input (removable plug)
Terminals No.
Usage
1
Earth Ground
2
Neutral (ground for DC controllers)
3
Line (+24vdc for DC controllers)
J7
Fault relay output (removable plug)
Terminals No.
Usage
N.O.
Opens when a fault occurs (or power off)
C.
Common for the relay
N.C.
Closes when a fault occurs
J6,J13,J14
Relay outputs, external relay inputs (removable plug)
Terminal No.
Usage
1,2
Safety relay N.O. output (dry contact)
3,4
Safety relay N.O. output (dry contact)
5,6,7
Auxiliary relay N.C., COM, N.O.
8,9
External relay checking option
120V ac applied across these terminals when external relay is de-energized
N.O. Normally Open
COM. = Common
N.C. = Normally Closed