Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and
never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each
direct vent gas appliance must use it's own separate vent system.

In addition to the requirements listed here, follow the requirements provided with the vent.

A firestop is required whenever the vent penetrates a floor or ceiling (or passes through
horizontal framing members). A thimble is required whenever the vent passes through a wall (or
horizontal framing members).

Venting installation instructions may be found at

www.duravent.com

. Keep the vent

instructions, along with this manual, with the appliance for future reference.

Approved Vent

This fireplace may only use the following vent components (8-5/8” / 6” external diameter co-
axial vent). These parts are available from Travis Dealers.

Simpson Part #

Travis Part #

6” Length

68GSS-06

98900024

12” Length

68GSS-12

98900023

24” Length

68GSS-24

98900022

36” Length

68GSS-36

98900021

48” Length

68GSS-48

98900020

4” to 8” Adjustable Length (Slip Connector)

68GSS-12A

98900025

45

°

Elbow

68GSS-L45

98900026

90

°

Elbow

68GSS-L90

98900027

Wall Thimble

68G-SS-WT

98900030

Fire Stop

68G-SS-FS

98900029

Elbow Strap

68G-SS-ES

98900028

Wall Strap

68G-SS-WS

98900031

Adjustable Roof Flashing (0/12 to 6/12)

68G-SS-F

98900035

Adjustable Roof Flashing (7/12 to 12/12)

68G-SS-SF

98900036

Storm Collar

68G-SS-SC

98900032

Vinyl Siding Stand-off

68GSS-VSS

98900037

Horizontal Termination

68G-SS-HC

98900033

Vertical Termination

68G-SS-VC

98900034

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found
that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.

Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.