Target indicators, Radio frequency interference (rfi), Isolation – Basler Electric BE1-51 User Manual

Page 57: Surge withstand capability, Ul recognized, Gost-r, Operating temperature, Storage temperature, Shock, Vibration

Advertising
background image

9137200997 Rev G

51

Target Indicators

Function targets may be specified as either internally operated or current operated by a minimum of 0.2
amperes through the output trip circuit. When current operated, the output circuit must be limited to 30
amperes for 0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.

Radio Frequency Interference (RFI)

Field-tested using a five-watt, hand-held transceiver operating at random frequencies centered around
144 MHz and 440 MHz, with the antenna located six inches from the relay in both horizontal and vertical
planes.

Isolation

In accordance with IEC 255-5 and ANSI/IEEE C37.90, one-minute dielectric (high potential) tests as
follows:
All circuits to ground ........................ 2,121 Vdc
Input to output circuits ..................... 1,500 Vac or 2,121 Vdc

Surge Withstand Capability

Qualified to ANSI/IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems.

UL Recognized

UL recognized per Standard 508, UL File No. E97033. Note: Output contacts are not UL recognized for
voltages greater than 250 volts and input power supply voltages greater than 150 volts.

GOST-R

GOST-R certified per the relevant standards of Gosstandart of Russia.

Operating Temperature

The operating temperature range is from

−40°C (−40°F) to +70°C (+158°F).

Storage Temperature

The storage temperature range is from

−65°C (−85°F) to +100°C (+212°F).

Shock

In standard tests, the relay has withstood 15 g in each of three mutually perpendicular planes without
structural damage or degradation of performance.

Vibration

In standard tests, the relay has withstood 2 g in each of three mutually perpendicular planes, swept over
the range of 10 to 500 Hz for six sweeps, 15 minutes each sweep without structural damage or
degradation of performance.

Weight

Single-Phase ................................... 13.0 lbs. (5.90 kg)
Two-Phase and Neutral .................. 14.0 lbs. (6.35 kg)
Three-Phase ................................... 14.0 lbs. (6.35 kg)
Three-Phase and Neutral ................ 14.4 lbs. (6.53 kg)

Case Size

S1 (Refer to the Installation chapter for case dimensions.)

BE1-51

Specifications