Introduction, Standard features, Time overcurrent functions – Basler Electric BE1-51 User Manual

Page 7

Advertising
background image

9137200997 Rev G

1

Introduction

BE1-51 Time Overcurrent Relays are microprocessor-based devices that monitor the magnitude of single-
phase, two-phase-and-neutral, or three-phase-and-neutral ac current to provide accurate time overcurrent
and instantaneous overcurrent protection for 50- or 60-hertz power systems.

Standard Features

Time Overcurrent Functions

Time overcurrent elements pick up over a range of 0.1 to 0.8 amperes, 0.3 to 2.4 amperes, 0.5 to 4.0
amperes, 1.5 to 12.0 amperes, 0.1 to 2.4 amperes, or 0.5 to 12.0 amperes and provide an adjustable time
delay that is proportional to the overcurrent. Time delay is initiated when the sensed current exceeds the
pickup point. When the current drops below the pickup point, the timing circuit is reset immediately. At
reset, the output contacts, if operated, are restored to normal.

Adjustment of the overcurrent pickup point is provided by controls on the relay front panel. Time delay is a
function of the characteristic curve that has been selected. Time delay is settable from 00 to 99 on the
TIME DIAL thumbwheel switch located on the front panel. Curve type is selected either as an option or, in
some models, is switch selectable.

Sixty-nine characteristic curves and three timing options are available:

Characteristic curves:

Seven inverse time

Nine I

2

t

Seven inverse time with extended timing range

Nine I

2

t with extended timing range

Five British Standard 142 (E curves)

Seven integrating inverse time

Nine integrating I

2

t

Seven integrating inverse time with extended timing range

Nine integrating I

2

t with extended timing range

Timing option Z1 (switch-selectable, 16-position) B and C curves:

Seven inverse time

Nine I

2

t

Timing option Z1 with option 2-D or 2-E (switch-selectable, 16-position) B and C curves:

Seven inverse time with extended timing range

Nine I

2

t with extended timing range

Timing option Z2 (switch-selectable, 16-position) B and E (British Standard 142) curves:

Seven inverse time

One I

2

t

Five British Standard (BS) 142 (E curves)

Timing option Z2 with option 2-D or 2-E (switch-selectable, 16-position) B and E (BS142) curves:

Seven inverse time with extended timing range

One I

2

t with extended timing range

Five British Standard 142 (E curves)

Timing option Z3 (switch-selectable, 16-position) integrating B and C curves:

Seven integrating inverse time

Nine integrating I

2

t

Timing option Z3 with option 2-D or 2-E (switch-selectable, 16-position) integrating extended B and C
curves:

BE1-51

Introduction