Bronkhorst DeviceNet slave interface User Manual

Page 10

Advertising
background image

BRONKHORST

®

 

Page 10   

 

 

 

 

DeviceNet interface 

 

 

 

9.17.026 

The distance between any two points must not exceed the maximum cable distance allowed for the data rate used. 
 

Data rate 

Maximum distance 

(flat cable) 

Maximum distance

(thick cable) 

Maximum distance

(mid cable) 

Maximum distance

(thin cable) 

125k bit/s 

420m 

500m

300m

100m 

250k bit/s 

200m 

250m

250m

100m 

500k bit/s 

75m 

100m

100m

100m 

 

 

2.5 D

ROP LINES WITH 

D

EVICE

N

ET

 

 
The cumulative drop line length refers to the sum of all drop lines, thick, thin, or mid cable, in the cable system. This 
sum cannot exceed the maximum cumulative length allowed for the data rate used. 
 

Data rate

Cumulative drop line length

125k bit/s

156m

250k bit/s

78m

500k bit/s

39m

 

 

The maximum cable distance from any device on a branching drop line to the trunk line is 6m.

 

2.6 N

ETWORK TERMINATION

 

 

 

You must terminate the trunk line at both ends with 121 Ohms, 1%, 1/4W terminating resistors. 

 

2.7 P

OWER 

S

UPPLY

 

 
The cable system requires the power supply to have a rise time of less than 250 milliseconds to within 5% of its rated 
output voltage. You should verify the following: 

 The power supply has its own current limit protection 
 Fuse protection is provided for each segment of the cable system 
 Any section leading away from a power supply must have protection 
 The power supply is sized correctly to provide each device with its 
 Required power 
 De‐rate the supply for temperature using the manufacturer’s guidelines 

 

 

Use the power supply to power the DeviceNet cable system only. If a device requires a separate 24V 
power source other than the DeviceNet power source, you should use an additional 24V power source. 

 

Choosing a Power Supply

The total of all of the following factors must not exceed 3.25% of the nominal 24V needed for a DeviceNet system.
initial power supply setting 

1.00%

line regulation 

0.30%

temperature drift (total) 

0.60%

time drift 

1.05%

load regulation 

0.30%

 

The maximum cable distance is not necessarily the trunk length only. It is the maximum distance 
between any two devices.

 

Advertising