Bronkhorst DeviceNet slave interface User Manual

Page 19

Advertising
background image

BRONKHORST

®

 

Page 19   

 

 

 

 

DeviceNet interface 

 

 

 

9.17.026 

3.4 P

OLLED 

I/O

 

 

3.4.1 Representation 

All of the above attributes in the tables from Table 2‐1 to Table 2‐16 can be accessed using Explicit Messaging. Upon 
existence of an explicit connection, a Polled I/O connection can also be established and coexist. Once the Polled I/O 
connection has been established, the device will be able to accept and process the Polled I/O requests. For example, if 
Instance #7 has been selected as Output IO Assembly Instance, two data bytes representing the new setpoint shall be 
appended  to  the  Polled  I/O  request  for  setting  a  setpoint.  If  the  Data  Unit  attribute  were  0x1001  as  the  code  for 
“Counts”, the value of the setpoint bytes will be an signed integer where 0x7D00 (*) represents 100% flow and 0x0000 
represents 0% flow. Upon reception of the Polled I/O Request, if Instance #2 has been selected as Input IO Assembly 
Instance  the DeviceNet  MFC will respond  with  a  Polled  I/O  Response carrying  with  it  three  data  bytes  as  described 
below: 

Polled I/O Response’s Data Field using Counts as Data Unit

Byte0: 

 Exception Status 

Byte1:  

Indicated Flow (LSB) 

Byte2:  

Indicated Flow (MSB) 

BYTE 

INT  (0x7D00 = 100%)

 

Polled I/O Request’s Data Field using Counts as Data Unit

Byte0:  

New Setpoint (LSB) 

Byte1:  

New Setpoint (MSB) 

INT  (0x7D00 = 100%) 


Note that if “Counts” has been selected for the Data Unit attribute of the Analog Sensor and Controller object (i.e., the 
value  of  these  attributes  is  0x1001),  then  the  Indicated‐Flow  bytes  in  the  Polled  I/O  Response  represent  the  same 
information as that of the New‐Setpoint bytes in the Polled I/O Request (i.e., 0x0000 represents 0% flow and 0x7D00 
(*) represents 100% flow). However, if the “Data Unit” attribute of the Sensor and the Setpoint object are 0x1400, the 
value of the indicated flow and setpoint will be in Standard Cubic Centimeter (SCCM). Note that the setpoint and the 
indicated flow can be set with different data unit (i.e., Counts for Setpoint and SCCM for Indicated‐flow or vice versa). 
Since the Indicated‐flow and Setpoint attribute are integer, if used in SCCM mode the value of these attribute can not 
exceed 32767 SCCM. Therefore the SCCM mode shall not be used for MFCs having gases with the full‐scale exceeding 
32767 SCCM or having the Full‐scale loaded with SLM data unit. 

Polled I/O Response’s Data Field using SCCM as Data Unit

Byte0: 

 Exception Status 

Byte1:  

Indicated Flow (LSB) 

Byte2:  

Indicated Flow (MSB) 

BYTE 

INT  (0 to Full Scale) 

 

Polled I/O Request’s Data Field using SCCM as Data Unit

Byte0:  

New Setpoint (LSB) 

Byte1:  

New Setpoint (MSB) 

INT  (0 to Full Scale) 


The tables above show some examples of the Polled I/O setting. There are eight (8) IO Assembly Instances that the 
user can choose from; 4 for input and 4 for output.  These instances are specified in the MFC Device Profile document. 
See next paragraph for more details. 
 
 
 

 

(*) 100% Measured Value indication for Bronkhorst instruments is 0x7D00 (signed integer).  Maximum 
value  for  Measured  Value  is  102.4  %,  which  is:  0x7FFF.  Other  suppliers  may  use  different  ranges  for 
Measured Value. Via Full Scale: attribute 0x0A of object 0x31, analog sensor, it is possible to readout 
the signed integer value used for 100%. 

 

Advertising