Bronkhorst DeviceNet slave interface User Manual

Page 16

Advertising
background image

BRONKHORST

®

 

Page 16   

 

 

 

 

DeviceNet interface 

 

 

 

9.17.026 

3.3.7 S‐Single Stage Controller Object 

Class Code 33 HEX 
The S‐Single Stage Controller Object models a closed‐loop control system within a device. 
 
 
 

CONTROLLER OBJECT’S INSTANCE ATTRIBUTES (Instance = 1)

SINGLE STAGE 

CONTROLLER 

OBJECT 

ATTRI‐

BUTE 

ATTRIBUTE NAME 

SERVICE 

CODE 

DATA TYPE 

FLOW‐

BUS 

Comment 

0x33 

0x01 

Number of 
Attributes 

0x0E 

USINT 

 

0x33 

0x02 

Attribute List 

0x0E

Array of USINT

0x33 

0x03 

Data Type 

0x0E, 0x10 

USINT 

 

0xC3=INT, 0xCA=REAL 

0x33 

0x04 

Data Units 

0x0E, 0x10 

UINT 

 

0x1001=counts, 0x1400=sccm, etc 

0x33 

0x05 

Control Mode 

0x0E, 0x10

USINT

0x33 

0x06 

Setpoint 

0x0E, 0x10 

INT or REAL

1

 

1,1 

See attribute 3 and 4. For data unit 
counts the setpoint attribute must be in 
the range of 0..32000. 
Where:  0 = min. setpoint (0%) 
 

32000 = max. setpoint (100%) 

0x33 

0x0A 

Status 

0x0E 

BYTE 

 

 

0x33 

0x13 

Ramp Rate 

0x0E, 0x10

UDINT

1,2

Setpoint slope in msec  
(max. 3000000 msec) 

 

 

1

 Depends on the value assigned to the Data Type attribute.  If the value of this attribute is 0xC3, the 

selected data type is Integer, and if the value of this attribute is 0xCA, the selected data type will be the 
IEEE‐754 single‐precision floating‐point. 

 

Advertising