Bronkhorst DeviceNet slave interface User Manual

Page 13

Advertising
background image

BRONKHORST

®

 

Page 13   

 

 

 

 

DeviceNet interface 

 

 

 

9.17.026 

3.3.4 Supervisor Objects 

Class Code 30 HEX 
This object models the interface, functions and behaviour associated with the management of application objects for 
devices within the “Hierarchy of Semiconductor Equipment Devices” 

SUPERVISOR OBJECT’S INSTANCE ATTRIBUTES (Instance = 1)

DEVICE 

SUPERVISOR 

OBJECT 

ATTRI‐

BUTE 

ATTRIBUTE NAME 

SERVICE 

CODE 

DATA TYPE 

FLOW‐BUS 

Comment 

0x30 

0x01  Number  of Attributes 

0x0E 

USINT 

 

20 

0x30 

0x02  Attribute List 

0x0E 

Array of USINT 

 

 

0x30 

0x03  Manufacturer’s Device Type

0x0E

SHORT‐STRING

113,1; Char[6]  “MFM" or "MFC”

0x30 

0x04  SEMI Standard Revision 

0x0E 

SHORT‐STRING

 

“E54‐0997” 

0x30 

0x05  Manufacturer’s Name 

0x0E

SHORT‐STRING

“Bronkhorst High‐Tech”

0x30 

0x06  Manufacturer’s Model # 

0x0E 

SHORT‐STRING 113,2; Char[14]   

0x30 

0x07  Digital MFC Software Revision 

Level 

0x0E

SHORT‐STRING

113,5; Char[5]  “V6.XX” 

0x30 

0x08  DeviceNet Hardware Revision 

Level 

0x0E 

SHORT‐STRING

113,7; Char[1]  “C” 

0x30 

0x09  Manufacturer’s Serial Number

0x0E

SHORT‐STRING 113,3; Char[20]  Unique serial nr. for BHT 

instruments 

0x30 

0x0A  Device Configuration 

0x0E 

SHORT STRING  113,4; Char[16]  Manufacturer configuration

0x30 

0x0B  Device Status 

0x0E

USINT

 

0x30 

0x0C  Exception Status 

0x0E 

BYTE 

 

 

0x30 

0x0D  Exception Detail Alarm 

0x0E

STRUCT

 

0x30 

0x0E  Exception Detail Warning 

0x0E 

STRUCT 

 

 

0x30 

0x0F  Alarm Enable 

0x0E, 0x10

BOOL

0‐1 

0x30 

0x10  Warning Enable 

0x0E, 0x10

BOOL 

 

0‐1 

0x30 

0x13  Last Maintenance Date 

0x0E 

DATE 

113,11; Char[8]  Service date 

0x30 

0x17  Running Hours 

0x0E

UDINT

118,2

0‐65535 

0x30 

0x64  Init Mode 

0x0E, 0x10

USINT 

0,10 

0,64,73,82 

0x30 

0x65  Monitor 

0x0E, 0x10

USINT

115,2

0: measure=setpoint

0x30 

0x66  Default_Inp_IO_Assembly_Inst 

0x0E, 0x10

USINT 

 

 

0x30 

0x67  Default_Outp_IO_Assembly_Inst 0x0E, 0x10

USINT

 

 
 

Device status 

Attribute value 

State 

Undefined

Self testing

Idle

Self test Exception

Executing

Abort

Critical fault

7‐50 

Reserved by CIP

51‐99 

Device specific

100‐255 

Vendor specific

 
 

Exception Status 

Bit 

Exception status bit map, Bit 7 set to 0

Function 

State 

Device specific definition 

Alarm/device‐common

Alarm/device‐specific

Alarm/manufacturer‐specific 

reserved – set to 0

Warning/device‐common 

Warning/device‐specific 

Warning/manufacturer‐specific 

0=basic method

1= Expanded Method

 

Advertising