Raised installation, Installation – Montigo R320 User Manual

Page 10

Advertising
background image

Figure 3. Fireplace installation, (Rough Frame-In dimensions).

Framing Dimensions

Model

Q

R

U

R-Series R320* 55" 47" **23¾"†
R-Series R420* 67" 47" **23¾"†

Determine the height of the platform based on where you want the

bottom edge of the glass to be, see

figure 1 or 1a for unit dimensions.

Maintain minimum ceiling height shown in table. Build fireplace frame

as shown in

figure 3.

Q (Opening)

R

(Opening)

U

3/4”
Plywood

Drywall
or Equiv.

Platform

** See Figure 1 or 1a.

† U is 29" for straight out the back vent run installations.

Raised Installation:

Maximum

Platform Height

Minimum Required

Ceiling Height

24"

8'

48"

10'

Figure 2b. Clearances for straight rear vented installation with PVHEX58-300.

24"

610

38 34 "

983

18 14 "

463

PVHFL58-300

Stud Wall

Rear

Fireplace

Floor

Header

Termination

Mounting

Flange

24"

610

34"

863

8"

203

PVHEX58-300

Stud Wall

Rear

Fireplace

Floor

Header

Termination

Mounting

Flange

Figure 2c. Clearances for straight rear vented installation with PVHFL58-300.

Note: Images are shown without screens for clarity purposes.

However, your fireplace should not be operated without proper

installation of screens.

R320 & R420 Power Vent Indoor Gas Fireplace

Page 10

XG0770 - 150105.1

Installation