Section 10: cleaning and maintenance, Notice, Maintenance – Montigo R320 User Manual

Page 32

Advertising
background image

General

Have the fireplace and installation inspected yearly. The

inspection must include, but is not limited to, the following:

• A visual check of the entire vent system and termination.

• An inspection of the door gaskets to ensure a proper seal.

• An inspection of the burner, vent run, and primary air

openings.

• An inspection of the gas valve, gas components, and pilot

flame. For your convenience a 1/8" manifold pressure tap

is supplied on the gas valve for a test gauge connection.

■ For

Natural Gas this appliance requires a minimum inlet pressure

of 5.5" W.C. and a manifold pressure of 3.5" W.C.

■ For

Propane Gas this appliance requires a minimum inlet

pressure of 11" W.C. and a manifold pressure of 10" W.C.

■ Always keep the fireplace area clear and free of combustible

materials, as well as gasoline and other flammable vapors and

liquids.

■ Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the

appliance and to replace any part of the control system and any

gas control which has been under water.

Cleaning

When the fireplace is first activated, there may be some smoking and

a visible film may be left on the glass. This is a normal condition, and

is the result of burning of protective coatings on new metal.
■ Glass must be cleaned periodically to remove any film (which is

a normal by-product of combustion) which may be visible. Film

can easily be removed by removing the door, as shown on Page

29. Handle the door carefully, and clean it with non-abrasive,

non-ammonia based glass cleaners. One of the most effective

products is Kel-Kem.

■ Silicone seals on inner door during initial firing will "off gas", leaving

a visual deposit of a white substance on combustion chamber

walls. This can easily be removed using normal household

products.

■ Use a vacuum cleaner or whisk broom to keep the control

compartment, burner, and firebox free from dust and lint.

Figure 23. Gas valve.

Gas Control Valve

Do not use ammonia based or abrasive cleaners on the glass, they will permanently

etch the surface. Use an approved gas fireplace glass cleaner such as Kel-Kem or

White off.

NOTICE

Bk

R

W

Honeywell (Q3450)

Pilot Assembly

Pilot Electrical

Harness Connector

Honeywell Gas

Control (SV9501M)

Gas Control

Connector

Section 10: Cleaning and Maintenance

Procedure for Checking Calibration of Flue Gas Switch

1). Disconnect power vent harness from the plug in the control box.
2). Turn wall switch 'ON'.
3). Monitor flue gas switch LED for 2 minutes and ensure LED

does not come on or the glow plug will not light during this period.
4). Reconnect power vent harness to plug in the control box.

R320 & R420 Power Vent Indoor Gas Fireplace

Page 32

XG0770 - 150105.1