Section 3-4: venting components, Installation – Montigo R320 User Manual

Page 20

Advertising
background image

The following components and associated Montigo part numbers are for

installation of a roof or wall mounted Power Vent. Only use Montigo Vent

Components. Use of non-Montigo parts will VOID the warranty and may impede

operation of the fireplace.

A - Termination

PVHEX58-300 Wall Mount 5"/8"

PVHFL58-300 Flush Wall Mount

5"/8"

PVVEX58-300 Roof Mount 5"/8"

C - Flex Sections

PFL1 (12" f/f Section)

PFL2 (24" f/f Section)

PFL3 (36" f/f Section)

PFL4 (48" f/f Section)

PFL6 (72" f/f Section)

D - Rigid Sections

PXT - 10 (10" f/f Section)

PXT - 20 (20" f/f Section)

PEXT - 1 (12" f/m Section)

PEXT - 2 (24" f/m Section)

PEXT - 3 (36" f/m Section)

PEXT - 4 (48" f/m Section)

PEXT - 6 (72" f/m Section)

E - Elbows

PEL-90MM (m/m 90º Elbow)

PEL-90FF ( f/f 90º Elbow)

PEL-90FM ( f/m 90º Elbow)

PEL-45FM ( f/m 45º Elbow)

F - Support Ring & Plate PSPXT-8
G - Firestop

FS-8

H - Heat Shield

RHS101

Connection and installation of the vent components should

adhere to the following guidelines:

„

Montigo recommends the use of a flex section for the final pipe

connected directly to the fireplace offering greater flexibility

of installation and absorption of movement.

„

Firestops must be installed as required by National & local

codes.

„

Montigo recommends that all exterior corners and joints be

sealed with exterior caulking. However, we encourage you

to consult your Building Envelope Engineer or Waterproofing

Consultant for further recommendations.

„

Use any combination of rigid and flex pipe as required and in

any orientation (Male connectors can face in any direction).

„

Flex sections may be stretched up to 50% of their total length

(e.g. a 24” section maybe stretched to 36”).

„

Ensure the pipe ends male to female slide in a minimum of

1 1/2” of overlap.

„

Connect all vent sections using a minimum of three sheet

metal screws on the outer pipe flue.

„

Ensure all horizontal runs are supported with a minimum of

3 supports per 10’ of venting.

„

When hanging/ supporting venting, ensure that 1” clearance

is maintained on sides and bottom of vent runs and 2” above

horizontal vent runs to any combustible material.

„

Rigid pipe may be cut less than half way from the

female

end only.

„

Ensure when cutting sections of rigid pipe to maintain integrity

of internal supports.

„

Place the springs, supplied with the pipe kit, between the

outer and inner pipes to keep the pipes separate and avoid

any possible hot spots.

IMPORTANT:

Please Refer to your Building Envelope

Engineer or Waterproofing Consultant

for a review of ALL penetrations through

exterior walls or the roof.

R320 & R420 Power Vent Indoor Gas Fireplace

Page 20

XG0770 - 150105.1

Installation

Section 3-4: Venting components