Section 3-5: Heat Shields

Installing a Wall Mounted RHS101 Heat shield

The RHS101 Heat shield

must be used if vent pipe passes through

a wall or ceiling within 6' of the unit.
To install the RHS101, Slide the Inner Section over the vent pipe

that will connect to the fireplace. Then fasten the vent pipe to the

back of the fireplace with a minimum of three sheet metal screws.

From the outside slide the RHS101 outer section on. To complete

the installation fasten the Heat Shield Outer Section & inner section

to the structure. See Figure 14.

Figure 14.

RHS101 Installation. (Install by sliding over vent pipe

where it passes through the combustible construction).

Outer Shield 10 1/4”

3/8” Min. Both sides Typical

3/8” Min.

3/8” Min .

Combustible Framing

12” x 12”

Inner Shield 9 3/8”

R320 & R420 Power Vent Indoor Gas Fireplace

Page 21

XG0770 - 150105.1

Installation