R320 & R420 Power Vent Indoor Gas Fireplace

Page 41

XG0770 - 150105.1

Appendix

PVHIN58-300 Inline Power Vent with TMHIN58-40 Termination

v

v

FIXED

CLOSED

OPERABLE

F

C

B

v

v

OPERABLE

FIXED

CLOSED

v

B

X

B

A

B

J

H

I

X

K

v

M

V

B

L

D

E

V

INSIDE

CORNER DETAIL

v

G

A

V VENTER TERMINAL

X AIR SUPPLY INLET

AREA WHERE TERMINAL IS

NOT PERMITTED

PVHIN58-300 / TMHIN58-40 Termination

A= Clearance above grade, veranda,

porch, deck, or balcony

12 in (30 cm)

12 in (30 cm)

Canadian Installations

US Installations

1

2

B= Clearance to window or door that

may be opened

6 in (15 cm) for appliances <

10,000 Btuh (3 kW), 12 in

(30 cm) for appliances >

10,000 Btuh (3 kW) and <

100,000 Btuh (30 kW), 36 in

(91 cm) for appliances >

100,000 Btuh (30 kW)

6 in (15 cm) for appliances <

10,000 Btuh (3 kW), 9 in

(23 cm) for appliances >

10,000 Btuh (3 kW) and <

50,000 Btuh (15 kW), 12 in

(30 cm) for appliances >

50,000 Btuh (15 kW)

C= Clearance to permently closed

window

B

B

6 in (38 cm)

D= Vertical clearance to ventilated

soffit located above the terminal within

a horizontal distance of 2 feet (61 cm)

from the center line of the terminal

6 in (38 cm)

E= Clearance to unventilated soffit

6 in (38 cm)

6 in (38 cm)

F= Clearance to outside corner

* (15 cm)

* (15 cm)

G= Clearance to inside corner

0 in (38 cm)

0 in (38cm)

H= Clearance to each side of center

line extended above meter/regulator

assembly

3 ft (91 cm) within a height 15

ft. (4.5 m) above the meter/

regulator assembly

*

I= Clearance to service regulator

vent outlet

3 ft (91 cm)

*

J= Clearance to nonmechanical air

supply inlet to building or the

combustion air inlet to any other

appliance

6in (15 cm) for appliances <

10,000 Btuh (3 kW), 12 in (30

cm) for appliances > 10,000

Btuh (3 kW) and < 100,000

Btuh (30 kW), 36 in (91 cm)

for appliances > 100,000

Btuh (30 kW)

Canadian Installations

US Installations

1

2

6in (15 cm) for appliances <

10,000 Btuh (3 kW), 9 in (23

cm) for appliances > 10,000

Btuh (3 kW) and < 50,000

Btuh (15 kW), 12 in (30 cm)

for appliances > 50,000 Btuh

(15 kW)

K= Clearance to a mechanical air

supply inlet

6 ft (1.83 m)

3 ft (91 cm) above if within 10

ft (3 m) horizontally

L= Clearance above paved sidewalk

or paved driveway located on

public property

7 ft (2.13 m)

*

M= Clearance under veranda porch

deck, or balcony

12 in (30 cm)

*

1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two

single family dwellings and serves both dwellings.

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath

the floor.

* For clearances not specified in ANSI Z223.1/NFPA or CSA B149.1, one of the following shall be

indicated

a) A minimum clearance value determined by testing in accordance with section 2.23.5, or;

b) A reference to the following footnote:

"Clearance in accordance with local installation codes and the requirements of the gas supplier"

Figure 27b. PVHIN58-300 Inline Power Vent with TMHIN58-40 Termination Locations