Section 3-3-2: venting layout, Installation – Montigo P52DF User Manual

Page 13

Advertising
background image

Page 13

P52DF* Indoor Gas Fireplace

XG0196 - 150204.3

Installation

Figure 11. 5"/8" Top Vent Venting Graph for wall mounted

terminations.

84”

96”

A

C

B

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting graph parame-

ters, please contact a local Montigo

Dealer for Power Venting options.

The Venting Graph:
Measure the vertical height from the fireplace hearth to the

centre of the termination and the horizontal run from the

fireplace flue collar to the wall flange of the termination. Plot

on the Venting Graph

Figure 11 with an 'X'.

If the 'X' falls on or above the top boundary of the shaded

area, the installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 120" and the

horizontal run to the wall flange of the vent termination

is 120", this would be an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 36" and the

horizontal run to the wall flange of the vent termination

is 84",

this would not be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is

60" and the horizontal run to the wall flange of the vent

termination is 144",

this would not be an acceptable

installation

.

Figure 11a. 5"/8" Top Vented, wall mounted installation with one

90° bend. The vent run must comply with Venting Graph for Top
vent, wall mounted terminations,

Figure 11

.

Section 3-3-2: Venting Layout:
Wall mounted termination.
Selection of components and details of venting layout

should adhere to the following guidelines:

„

Vent terminations must not be recessed in walls or

siding.

„

For Heat Shield requirements see

Section 3-3-3.

„

Once the proposed venting layout has been

determined refer to

Figure 11 or 12 to ensure the

layout is acceptable.

Notes Wall Mounted Terminations: 5"/8" TOP VENT

„

All measurements for vertical or horizontal runs are

measured from center of the vent pipe.

„

Venting runs must fall within the limits set by the

venting graph, see

Figure 11

Wall mounted Terminations
The following details are some possible configurations for

Wall mounted terminations.

Heat Shield

Termination

Hearth

Exterior

Wall

Flex section

7’ Max. for min Vertical

8’ Min.

Note: Images are shown without screens for clarity

purposes. However, your fireplace should not be operated

without proper installation of screens.