Section 3: venting, Section 3-1: converting to rear vent, Section 3-1-1: converting to 5"/ 8" venting – Montigo P52DF User Manual

Page 9: Section 3-1, Converting to rear vent, Installation

Advertising
background image

Page 9

P52DF* Indoor Gas Fireplace

XG0196 - 150204.3

Installation

Section 3: Venting

Figure 7. Flue cover and collar removal, Top Vented

fireplace.

Figure 7a Flue cover and collar installation, Rear Vented

fireplace.

Montigo supplies a variety of direct venting and termination

options.

The direct vent termination location MUST be

selected such that it is the highest point in the venting

assembly. It should also be selected such that it provides

the shortest vent run possible. Should it be impossible to

ensure that the termination is the highest point or to meet

the venting guidelines laid out below please contact your

Montigo dealer to discuss power venting options.

NOTES FOR PLANNING VENTING:

Venting can originate from the unit through the top or

through the rear
Venting can terminate through the roof or through an

exterior wall.
Refer to Appendix A - Termination Locations to ensure

the planned termination location is acceptable.
Once the termination location has been established,

refer to the appropriate section below for installation

details
All fireplaces shipped from the factory are Top vent

with 5" and 10" collar installed.
Silicone application is not required when joining

Montigo vent pipes and components.

UNITS CANNOT BE REAR VENTED

STRAIGHT THROUGH THE WALL.

REAR VENT APPLICATIONS MUST BE

MULTI-ELBOW.

5” Inner Flue Collar

Outer Flue Collar

Flue Gasket

Flue Cover Plate

10”

Flue Gasket

Flue Cover Plate

10”Outer Flue Collar

5” Inner Flue Collar

Note: Images are shown without screens for clarity

purposes. However, your fireplace should not be operated

without proper installation of screens.

Section 3-1:

Converting to Rear Vent

Use the following instructions to convert a

P52DF* for

Rear Vent use:

1. Remove the Rear flue cover and gasket (5" and 10")

on the flue outlet, as shown in

Figure 9.

2. Next, Remove the Top flue collar's (5" and 10") on the

flue outlet, as shown in

Figure 9

3. Install the (removed) Rear flue cover and gasket

material, to the Top vent outlet. Fasten the cover with

included hardware, as illustrated

Figure 10.

Section 3-1-1: Converting to 5"/ 8" Venting

(VERTICAL VENT RUNS OVER 8' FROM TOP OF

UNIT ONLY)

Use the following instructions to convert a

P52DF* from

5"/ 10" to 5"/ 8" venting for Top or Rear Vent use

outside of 8 feet vertically from the unit:

1. Remove the 10" outer flue collar on the flue outlet,

from the desired vent start - TOP or REAR

2. Install the separately ordered 8" reducing collar

(

RVA108) on the Top or Rear vent outlet.

Note: If power venting, vent run must be reduced to 5"/8"

or 4"/7". contact your Montigo dealer to discuss power

venting options.