Clearances, Installation – Montigo P52DF User Manual

Page 8

Advertising
background image

Page 8

P52DF* Indoor Gas Fireplace

XG0196 - 150204.3

Installation

Clearances:
When installing a shelf over the top of the fireplaces, the

following guidelines must be adhered to:
For Rear Vent multi-elbow applications, the minimum

clearance is 1" from the elbow off the rear of the fireplace to

a wall, or any combustible materials, and 12" clearance from

the top of the fireplace to the underside of any combustible

shelf materials.
For Top Vent applications, the minimum clearance is 1"

from the rear of the fireplace to a wall, or any combustible

materials, and 26" to the underside of any combustible

shelf materials.
1” clearance is maintained on sides and bottom of vent

runs and 2” above horizontal vent runs to any combustible

material.

MODEL

Top - T

op vent

Top - Rear vent

Rear

Sides

††

Floor

Mantel

P52DF*

26"

12" 1" 2 1/2"

0"

See

Section 6

Finishing

around the

fireplace

NOTES:
† Clearance from top of fireplace to a ceiling within the

fireplace enclosure.

†† 2 1/2" clearance is from the main body of the firebox, NOT

the insulated flange. Clearance to the insulated flange is 1".

Figure 6d. Securing the Nailing Flange Extension.

Installing the Nailing Flange Extension

(Part No. P52087)

The supplied nailing extension must be placed along the top

edge of the fireplace and securely fastened into place, as

shown in

figure 6d. Note: The nailing flange extension can

be substituted with a piece of

NON-Combustible material

of the same size and thermal characteristics, ie: cement

board or equivalent.

4"

Before installing the supplied nailing flange extension, fold

tabs at bottom of nailing flange to a 90 degree angle.

Figure 6a. Bottom of Nailing Flange Extension

Figure 6b. Bottom of Nailing Flange Extension with tab

folded at 90 degree angle

Figure 6c. Insert folded tabs into slots above the front of

the fireplace

Front of Nailing Flange

Front of Fireplace

Installing The Standoffs

To avoid elevated mantel temperatures, all

P52DF* gas

fireplaces are required to have the supplied standoffs installed.

The fireplace is supplied with two standoffs. Bend and install

these standoffs on top of the fireplace ensuring that the

height of the standoff maintains a 7 ½" clearance.

7 ½”

Figure 6. Installing standoffs