Section 5: installing the gas line, Section 5-1: fuel conversion, Section 5-2: gas pressure – Montigo P52DF User Manual

Page 19: Section 5-3: gas connection, Warning, Installation

Advertising
background image

Page 19

P52DF* Indoor Gas Fireplace

XG0196 - 150204.3

Installation

Section 5: Installing the Gas Line

WARNING

When installing the fireplace - gas lines, fittings,

accessories or any other objects cannot impede the

proper movement of the door buckles.

NOTE: After gas line is connected, each appliance

connection, valve and valve train must be

checked while under normal operating pressure

with either a liquid solution, or leak detection

device, to locate any source of leak. Tighten

any areas where bubbling appears or leak is

detected until bubbling stops completely or leak

is no longer detected.

DO NOT use a flame of

any kind to test for leaks.

WARNING!

When pressure testing the fireplace, Gas line, and input

system follow the appropriate local codes or your area.

DO NOT connect the fireplace to pressures in excess

of 1/2lb. This will damage the gas control valve.

Figure 19. Gas line access.

Section 5-1: Fuel Conversion

■ Verify that your fireplace is compatible with your

available gas type. (Natural Gas or Propane shown

by "N" or "L" in your model number

■ If gas type is not compatible, contact your local Montigo

representative.

■ Conversion kits must be installed by a qualified service

technician.

Section 5-2: Gas Pressure

■ Optimum appliance performance requires proper

input pressures.

■ Gas line sizing requirements will be determined in

ANSI Z223.1 National Fuel Gas Code in the USA

and CAN/CGA B149 in Canada.

Pressure requirements are:

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.5in. w.c.

11in. w.c.

Manifold pressure

3.5in. w.c.

10in. w.c.

■ The manifold outlet pressure is set from the factory

to the appropriate pressure but should be verified.

■ To check pressures, control valves have a provision

to remove a 1/8” N.PT. plug to be fitted with a hose

barb.

■ Montigo requires a service shut off valve be located

in an accessible location to isolate the gas supply.

Only install gas shut-off valves approved for use by

the state, province, or other governing body in which

the fireplace is being installed.

Section 5-3: Gas Connection

■ See Figure 19 for location of gas line access.

■ Flexible gas connectors must not exceed 3 feet in

length, unless allowable within local regulations.

■ Connect incoming gas line to the 1/2"or 3/8" gas inlet

port.

■ Purge all air out of gas line.

■ Check appliance connection, valve and valve train

under normal operating pressure with a commercially

available leak check solution.

DO NOT USE A FLAME OF ANY KIND TO TEST FOR

LEAKS.

1¼”

2”

10½”

An inspection of the explosion relief flappers and door

MUST be

made prior to lighting the fireplace. A faulty seal on the door gasket

and/or explosion ports will result in products of combustion leaking into

the living space and may result in carbon monoxide poisoning.

WARNING: