P52DF* Indoor Gas Fireplace

XG0196 - 150204.3

Installation

Section A: Before You Start

IMPORTANT MESSAGE: SAVE THESE INSTRUCTIONS
The P Series

P52DF* Direct Vent fireplace must be installed

in accordance with these Instructions. Carefully read all

the Instructions in this manual first. Consult the Local Gas

Branch to determine the need for a permit prior to starting

the installation. It is the responsibility of the installer to

ensure this fireplace is installed in compliance with the

manufacturers instructions and all applicable codes.

BEFORE YOU START:

Installation Checklist

„

Determine the desired install location of your fireplace.

„

See

Section 1, Dimensions on Page 5, and refer to

the Framing

Section 2 for details.

„

Select the location of your termination and resulting

vent run.

„

Your selected termination location must be the

highest point in the Direct Vent installation.

„

Should it be impossible to meet the venting

requirements laid out in

Section 4: Venting, please

contact a local Montigo dealer regarding the use of

a Montigo Power Vent.

„

Lay out the Vent run; calculating the required elbows

and straight runs of 5"/10" (5"/8" if applicable) flex

and/or rigid pipe.

„

Layout Electrical Requirements Refer to

Section 5:

Wiring, for Details.

„

Refer to

Section 6: Installing the Gas Line, for details

on the gas connection and access.

„

Refer to local codes and guidelines for installation

requirements.

„

Installation and repairs should be done by a

qualified contractor and must conform to:

Installations in Canada must conform to the local

codes or in the absence of local codes to the current version

of Natural Gas and Propane Installation Code, CSA B149.

Electrical Installations must conform to the local codes or,

in the absence of local codes, to the current version of

Canadian Electrical Code, CSA C22.1.1

Installations in the USA must conform to the local

codes or in the absence of local codes to the current

version of National Fuel Gas Code, ANSI Z223.1/NFPA 54.

Electrical Installations must conform to the local codes or,

in the absence of local codes, to the current version of the

National Electrical Code, ANSI/NFPA 70. See

Appendix

C for installation within the State of Massachusetts.

Due to high operating temperatures, this appliance should be located out of traffic &

away from furniture and draperies.

Children and adults should be alerted to the hazards of the high surface temperature,

which could cause burns or clothing ignition.

Young children should be carefully supervised when they are in the same room as the

appliance.

Clothing or other flammable materials should not be placed on or near the appliance.

CAUTION

When this appliance is installed directly on any combustible material other than wood

flooring, it must be installed on a metal or wood panel extending the full width and

depth of the appliance or a fire will occur causing serious injury, property damage or

even death.

DANGER

Installation and repairs should be done by an authorized gas fireplace service technician.

The appliance should be inspected before use and at least annually by a professional. More

frequent cleaning may be required due to excessive lint from carpeting, bedding material,

etc. It is imperative that control compartments, burners and circulating air passageways of

the fireplace are kept clean.

NOTICE

WARNING

A barrier designed to reduce the risk of burns from hot viewing glass is provided with this

appliance and shall be installed for the protection of children and other at-risk individuals.

If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s

barrier for this appliance.

WARNING

Any safety screen, guard, or barrier removed for servicing an appliance must be replaced

prior to operating the appliance.