2 set the ip address using an eia-232 connection, Set the ip address using an eia-232 connection – RLE Protocol Converter V.2.4 User Manual

Page 24

Advertising
background image

24

Protocol Converter User Guide

800.518.1519

3

Configuration

3.1.2 Set the IP Address Using an EIA-232 Connection

To use the EIA-232 interface to set the Protocol Converter’s IP address:

1

Connect the EIA-232 port on the Protocol Converter to a terminal or PC running terminal

emulation software (HyperTerminal) with a 9-pin, male-female, straight-through serial

cable.

2

Set the appropriate communication port to 9600 baud, no parity, 8 data bits, 1 stop bit,

(9600/N/8/1), and no software or hardware flow command.

3

Once the terminal emulation software starts, press Enter on the keyboard.

The Protocol Converter’s boot prompt appears, (FDS_PC>).

NOTE

If the Protocol Converter’s boot prompt does not appear, check the communication settings

and make sure the unit is powered on.

4

From the boot prompt, type IP, one space, and the new IP address for the Protocol

Converter, then press Enter.

Example:

IP 192.168.103.211

The Protocol Converter reboots after the IP address is changed.

5

If you need to change the subnet mask: From the boot prompt type NM, one space, and the

new Subnet Mask address for the FDS-PC, then press Enter.

Example:

NM 255.255.255.0

The Protocol Converter reboots after the Subnet Mask is changed.

6

If you need to change the default gateway: From the boot prompt, type DG, one space, and

the Default Gateway address for the Protocol Converter, then press Enter.

Example:

DG 192.168.103.1

The Protocol Converter reboots after the Default Gateway is changed.

The Protocol Converter IP address is now set, and it can be accessed through a Web

browser using the new IP address. The default username is fds. There is no password; leave

that field blank.

Advertising