RLE Protocol Converter V.2.4 User Manual

Page 36

Advertising
background image

36

Protocol Converter User Guide

800.518.1519

3

Configuration

Bitflag

The proper bit flag to be used for this particular register.

Choose values from :00 to :15.

Modbus Word Order

Determines the way the register is read by the Protocol

Converter. Choose from Big-Endian (Left to Right) or Little-

Endian (Right to Left).

Gain

The gain value of the raw data being received. Set this

value only if necessary.

Offset

The offset value to the calculated reading for the register.

Set this value only if necessary.

Label

Designate a name (label) for the register being configured.

Labels can be up to 30 alphanumeric characters in length.

HTML Display

This option allows you to choose how the value is

displayed on the register page. Choose from Integer (whole

number) or Float (a number plus a decimal).

Threshold 1

Indicates the value that, when reached or exceeded,

causes the Protocol Converter to trigger an alarm.

Specify if the alarm should occur when the reading is less

than (<), Equal to (=) or greater than (>) the specified

threshold value.

Threshold 2

Indicates the value that, when reached or exceeded,

causes the Protocol Converter to trigger an alarm.

Specify if the alarm should occur when the reading is less

than (<), Equal to (=) or greater than (>) the specified

threshold value.

Alarm Delay

The amount of time, in seconds, that passes between the

time an alarm condition occurs and the time the Protocol

Converter issues an alert.

The default value of 0 indicates no delay.

Offline Delay

The amount of time, in seconds, that elapses before the

Protocol Converter considers the register to be stalled or

offline.

The default value of 0 indicates no delay.

Current Age

Indicates the amount of time, in seconds, since the

Protocol Converter last received an updated value.

Local Modbus Int Register

The Modbus Integer data (whole number) used by a master

device polling the Protocol Converter.

Local Modbus Float

Register

The Modbus Float data (number with decimal) used by a

master device polling the Protocol Converter.

Option

Description

Table 3.5

Modbus Register Configuration Page Options