Configure slave devices, Figure 3.11 device configuration screen, Table 3.4 – RLE Protocol Converter V.2.4 User Manual

Page 31: Device configuration fields

Advertising
background image

rletech.com

Protocol Converter User Guide

31

3

Configuration

3.5.

Configure Slave Devices

Once the basic functionality of the Protocol Converter has been configured, you’re ready to

configure slave devices. You can configure up to 32 slave devices to the Protocol Converter.

1

From the top navigation bar on the Protocol Converter’s home page, click the Device

Configuration link.

The Device Configuration page is divided into four subpages - eight slave devices can be

configured on each page. These slave devices can be configured for Modbus RTU/485,

Modbus TCP, SNMP V1, BACnet/IP, SNMP-RFC1628, or SNMP V2C.

Figure 3.11

Device Configuration Screen

2

To configure a slave device, enter the appropriate information for the communication

protocol used by that device. Only the applicable fields for each communications protocol

will appear. Configurable fields include:

Option

Description

Access Mode

Use the drop-down to select Modbus-RTU/485, Modbus

TCP, SNMP V1, BACnet/IP, SNMP-RFC-1628, or SNMP

V2.
Note: RFC-1628 access mode is available for BACnet/IP

only.

EIA-485 Port

Select the appropriate port.

Modbus/TCP Poll Rate

Select the number of packets per second - 10, 5, or 1.

Table 3.4

Device Configuration Fields