Configuration

3.6.

Configure Device Registers

Once the desired slave devices have been configured on the Protocol Converter, you can

program registers to those slave devices for the proper information to be polled. First, you can

select whether or not to enable write operations to the slave devices, then you can program the

registers.

NOTE

You can also delete the Protocol Converter’s entire register set. Make sure to consider this

operation carefully before carrying it out.

3.6.1 Enable Write Operations to Devices

To enable the ability to write values to Modbus, SNMP, and BACnet device registers:

1

Click the Configuration link in the menu bar. From the Configuration menu, click the

EIA-485/Modbus/BACnet-MSTP Ports link.

2

In the top section of the EIA-485/Modbus/BACnet-MSTP Ports page, select Yes to enable

the Device Write option:

The write operations are generated via Modbus preset single-register commands, SNMP

sets, and BACnet write-property operations. Refer to the following sections on configuring

Modbus, SNMP, and BACnet registers for more information about generating write

operations through the Protocol Converter’s user interface.