Figure 3.14 register configuration navigation – RLE Protocol Converter V.2.4 User Manual

Page 37

Advertising
background image

rletech.com

Protocol Converter User Guide

37

3

Configuration

2

Click Submit Changes located in the upper left hand corner of the web page.

3

Once the changes have been accepted, click the Next>> link in the bottom navigation bar to

configure the next register.

You can also click the First, <<Prev, Last, or End links to go to those locations in the list of

registers.

Figure 3.14

Register Configuration Navigation

BACnet Instance

The number used by a BACnet master for polling data from

the Protocol Converter.

Possible values include Analog Instance (AI) or Binary

Instance (BI).

BACnet Engineering Units

In the BACnet ASHRAE standard, numbers correlate with

units of measure. Refer to the BACnet ASHRAE standard

for more information.

BACnet COV Client
(COV - Change of Value)

The IP address of the BACnet master that is polling the

FDS-PC.

BACnet COV SPID

Enter the Subscriber Process Identifier.
You’ll also need to designate if it should be Confirmed or

Unconfirmed.
Confirmed: When a change of value is sent to the device, it

will look for an acknowledgement of the change to be sent

in response. If no acknowledgement is received, the

change will be sent again. This cycle will repeat until an

acknowledgement is received.
Unconfirmed: A change of value is sent, and the device

doesn’t look for an acknowledgement.

Select the Confirmed or Unconfirmed radio button to

indicate your preference.

BACnet COV Increment

Amount that the present value of a point needs to change

before the change of value message is initiated to the

BACnet master.

BACnet COV Period

Interval, in seconds, between polling operations.

SNMP register/Table OIDs

The OID (object identifier) being polled from the SNMP

software. The Protocol Converter displays the OIDs used

for Integer data, Float data, and the Label assigned.

SNMP Modbus Device

Register/Table OIDs

Formatted to

BASE.DEVICENUMBER.REGISTERNUMBER where

BASE is the OID for this table, DEVICENUMBER is the

device’s number in the Protocol Converter (1-32) and the

REGISTERNUMBER reflects the appropriate device point

address.

Option

Description

Table 3.5

Modbus Register Configuration Page Options