RLE Protocol Converter V.2.4 User Manual

Page 43

Advertising
background image

rletech.com

Protocol Converter User Guide

43

3

Configuration

2

Click Submit Changes located in the upper left hand corner of the web page.

HTML Display

This option allows you to choose how the value is

displayed on the register page. Choose from Integer (whole

number) or Float (a number plus a decimal).

Threshold 1

Indicates the value that, when reached or exceeded,

causes the Protocol Converter to trigger an alarm.

Specify if the alarm should occur when the reading is less

than (<), Equal to (=) or greater than (>) the specified

threshold value.

Threshold 2

Indicates the value that, when reached or exceeded,

causes the Protocol Converter to trigger an alarm.

Specify if the alarm should occur when the reading is less

than (<), Equal to (=) or greater than (>) the specified

threshold value.

Alarm Delay

The amount of time, in seconds, that passes between the

time an alarm condition occurs and the time the Protocol

Converter issues an alert.

The default value of 0 indicates no delay.

Offline Delay

The amount of time, in seconds, that elapses before the

Protocol Converter considers the register to be stalled or

offline.

The default value of 0 indicates no delay.

Current Age

Indicates the amount of time, in seconds, since the

Protocol Converter last received an updated value.

Local Modbus Int Register

The Modbus Integer data (whole number) used by a master

device polling the Protocol Converter.

Local Modbus Float Register

The Modbus Float data (number with decimal) used by a

master device polling the Protocol Converter.

BACnet Instance

The number used by a BACnet master for polling data from

the Protocol Converter.

Possible values include Analog Instance (AI) or Binary

Instance (BI).

SNMP Register/Table OID

The OID (Object Identifier) being polled from a SNMP

software. The Protocol Converter displays the OIDs used

for Integer data, Float data and the Label assigned.

SNMP Modbus Device

Register/Table OID

Formatted to

BASE.DEVICENUMBER.REGISTERNUMBER where

BASE is the OID for this table, DEVICENUMBER is the

device’s number in the Protocol Converter (1-32) and the

REGISTERNUMBER reflects the appropriate device point

address.

Option

Description

Table 3.7

BACnet Register Configuration Options (continued)

Advertising