TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

List of error codes

ERROR Nr.

DESCRIPTION

2

Illegal data address

3

Illegal data value

9

Illegal number of data required

10

The bit or word indicated cannot be modified

50

The procedure cannot be initiated because another procedure is in pro-
gress

51

The procedure cannot be initiated because the first part of SMART
algorithm (TUNE) is in progress

52

The procedure cannot be initiated because it is not elapsed 5 minutes
from power on or from end of another procedure

53

The procedure cannot be initiated because the probe temperature is less
than 1000°F/538°

54

The procedure cannot be initiated because the probe output is less than
1000 mV

55

The procedure cannot be initiated because the probe output is unstable
(drift > 10 mV/minute)

101

Error on configuration group 1

102

Error on configuration group 2

103

Error on configuration group 3

104

Error on configuration group 4

105

Error on configuration group 5

106

Error on configuration group 6

151

Error on control mode group 1

152

Error on control mode group 2

153

Error on control mode group 3

154

Error on control mode group 4

155

Error on control mode group 5

156

Error on control mode group 6

157

Error on control mode group 7

158

Error on control mode group 8

159

Error on control mode group 9

160

Error on control mode group Hidden

200

Error on main probe input calibration (0

÷

1.5 V)

201

Error on main probe input calibration (1

÷

1.3 V)

202

Error on TC input calibration (0

÷

60 mV)

203

Error on CJ calibration

204

Error on auxiliary input current (0

÷

20 mA) calibration

205

Error on auxiliary input voltage (0

÷

5 V) calibration

206

Error on auxiliary input voltage (0

÷

10 V) calibration

207

Error on Out 6 (0

÷

20 mA output) calibration

208

Error on Out 7 (0

÷

20 mA output) calibration