TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

Function code 6: Single word writing

By using this command, the master unit can change the value of one word (16 bit) of the
slave unit.

Command from master to slave

Reply from slave to master

Range

Byte

Range

Byte

Slave address (0*-255)

1

Slave address (1-255)

1

Function code (06)

1

Function code (06)

1

Word address (high byte)

1

Word address (high byte)

1

Word address (low byte)

1

Word address (low byte)

n

Data

2

Data

2

Error check (CRC-16) (low byte)

1

Error check (CRC-16) (low byte)

1

Error check (CRC-16) (high byte)

1

Error check (CRC-16) (high byte)

1

* To use the address 0, see note 1 at page 12: “Broadcast address”.

The 8000h value, present in the “data” field, should be considered as a don’t care value,
that is, the value present in the device at this address will not be modified.

Example:
Set word 2006 (7D6h) of slave at address 5 (5h) with value 1250 (4E2h)

Command from master to slave

Reply from slave to master

Range

Byte

Range

Byte

Slave address

05h

Slave address

05h

Function code

06h

Function code

06h

Word address (high byte)

07h

Word address (high byte)

07h

Word address (low byte)

D6h

Word address (low byte)

D6h

Data

04h

Data

04h

Data

E2h

Data

E2h

Error check (CRC-16) (low byte)

EAh

Error check(CRC-16) (low byte)

EAh

Error check (CRC-16) (high byte)

4Bh

Error check (CRC-16) (high byte)

4Bh