Super Systems AC20 RS485 Modbus User Manual

Page 42

Advertising
background image

Page 42/59

TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS

“AC.Cn.” - Menu conf. 4 - AUXILIARY CONTROL OUTPUT CONFIGURATION

ADDRESS

(decimal)

DEC.

Display

R

W

R

JBus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

2301

2300

Smart function

Range

0 = Smart function disable
1 = Smart function may be enabled

N.A.

(“Sñ.Fn”)

x

x

2302

2301

Control action type

Range

0 = The process is controlled by PID
actions
1 = The process is controlled by PI actions

N.A.

(“Cn.tP”)

x

x

2303

2302

Manual function

Range

0 = Manual function disabled
1 = Manual function enabled

N.A.

(“ñAn.F”)

x

x

2304

2303

Output value for transfer from auto to
manual

Note:

The value 7FFFh means that the transfer
from auto to manual is bumpless

1

(“Añ.UL”)

x

x

2305

2304

Manual/auto transfer type

Range

0 = Bumpless balance transfer
1 = Bumpless balanceless transfer

N.A.

(“ñ.A.t.t”)

x

x

2306

2305

Device status at start up

Range

0 = It starts always in auto mode
1 = It starts always in manual mode with
power output set to 0
2 = It starts in the same way it was left
prior to power shut down (if in manual
mode the power output is set to 0)
3 = It starts in the same way it was left
prior to power shut down (if in manual
mode the power output will be the last
value prior to power shut down)

N.A.

(“St.Fn”)

x

x