Super Systems AC20 RS485 Modbus User Manual
Page 24
Page 24/59
TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1
WORDS FOR DEVICE IN CONTROL MODE - PARAMETERS
“tiñE” - Menu group 8 - TIMERS SETTING
ADDRESS
(decimal)
DEC.
Display
R
W
R
JBus
Mod
Bus
DESCRIPTION
FIGU-
RES
MNEM
CODE
E
A
D
I
T
E
1301
1300
Timer for burn-off (in seconds)
0
(“t.bOF”)
x
x
1302
1301
Timer for purge (in seconds)
0
(“t.PrG”)
x
x
1303
1302
Timer for automatic burn-off interval (in
minutes)
Note:
The value 7FFFh means that no time
interval is imposed
0
(“bF.tr”)
x
x
1304
1303
Timer for probe test interval (in minutes)
Note:
The value 7FFFh means that no time
interval is imposed
0
(“Pb.tr”)
x
x
1305
1304
Time lasting to beginning of burn-off
procedure (in minutes)
Note:
The value 7FFFh means that no time
interval is imposed
0
(“bF.ñn”)
x
1306
1305
Time lasting to beginning of probe test
procedure (in minutes)
Note:
The value 7FFFh means that no time
interval is imposed
0
(“Pb.ñn”)
x