Super Systems AC20 RS485 Modbus User Manual

Page 38

Advertising
background image

Page 38/59

TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS

“Out.” - Menu Conf. 2 - OUTPUT CONFIGURATION

ADDRESS

(Decimal)

DEC.

Display

R

W

R

Jbus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

2101

2100

Out 1 function

Range:

0 = Output not used
1 = Time proportional main control output
2 = Time proportional secondary control
output
3 = Output used as alarm 1 output

N.A.

("O1.Fn")

x

x

2102

2101

Out 2 function

Range:

0 = Output not used
1 = Time proportional main control output
2 = Time proportional secondary control
output
3 = Output used as alarm 2 output

N.A.

("O2.Fn")

x

x

2103

2102

Out 3 function

Range:

0 = Output not used
1 = Time proportional main control output
2 = Time proportional secondary control
output
3 = Output used as alarm 3 output

N.A.

("O3.Fn")

x

x

2107

2106

Out 6 function

Range:

0 = Output not used
1 = Linear main control output
2 = Linear secondary control output
3 = Process variable retransmission
4 = Operative set point retransmission

N.A.

("O6.Fn")

x

x

2108

2107

Out 6 range

Range:

0 = 0 ÷ 20 mA
1 = 4 ÷ 20 mA

N.A.

("O6.rn")

x

x

2109

2108

Retransmission low scale range value for
Out 6

See Mbus

word 300

(“O6.Lr”)

x

x

2110

2109

Retransmission high scale range value
for Out 6

See Mbus

word 300

(“O6.Hr”)

x

x

2111

2110

Time constant for filter on Out 6 analog
retransmission value (in seconds)

0

(“O6.FL”)

x

x

Advertising