Super Systems AC20 RS485 Modbus User Manual

Page 39

Advertising
background image

Page 39/59

TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS

“Out.” - Menu Conf. 2 - OUTPUT CONFIGURATION

ADDRESS

(Decimal)

DEC.

Display

R

W

R

Jbus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

2112

2111

Out 7 function

Range:

0 = Output not used
1 = Linear main control output
2 = Linear secondary control output
3 = Process variable retransmission
4 = Operative set point retransmission

N.A.

(“O7.Fn”)

x

x

2113

2112

Out 7 range

Range:

0 = 0 ÷ 20 mA
1 = 4 ÷ 20 mA

N.A.

(“O7.rn”)

x

x

2114

2113

Retransmission low scale range value for
Out 7

See Mbus

word 300

(“O7.Lr”)

x

x

2115

2114

Retransmission high scale range value
for Out 7

See Mbus

word 300

(“O7.Hr”)

x

x

2116

2115

Time constant for filter on Out 7 analog
retransmission value (in seconds)

0

(“O7.FL”)

x

x

Advertising