TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONTROL MODE - PARAMETERS

“A.Ctr” - Menu group 5 - AUXILIARY CONTROL PARAMETERS

ADDRESS

(decimal)

DEC.

Display

R

W

R

JBus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

1001

1000

Anti-reset windup

0

(“ArU”)

x

x

1004

1003

Main control output low limit

1

(“ñ.OLL”)

x

x

1005

1004

Main control output high limit

1

(“ñ.OLH”)

x

x

1006

1005

Main control output max rate of rise

Note:

The value 7FFFh means that no ramp li-
mitation is imposed.

1

(“ñ.rñP”)

x

x

1007

1006

Proportional cycle time on main control
output (in seconds)

0

(“ñC.CY”)

x

x

1008

1007

Secondary control output low limit

1

(“S.OLL”)

x

x

1009

1008

Secondary control output high limit

1

(“S.OLH”)

x

x

1010

1009

Secondary control output max rate of
rise

Note:

The value 7FFFh means that no ramp li-
mitation is imposed

1

(“S.rñP”)

x

x

1011

1010

Proportional cycle time on secondary
control output (in seconds)

0

(“SC.CY”)

x

x

1012

1011

Set point low limit

See Mbus
Word 300

(“rL”)

x

x

1013

1012

Set point high limit

See Mbus
Word 300

(“rH”)

x

x

1014

1013

Rate of change for positive set point va-
riation

Note:

The value 7FFFh means that the transfer
is done as a step change.

See Mbus
Word 300

(“Grd1”)

x

x

1015

1014

Rate of change for negative set point va-
riation

Note:

The value 7FFFh means that the transfer
is done as a step change

See Mbus
Word 300

(“Grd2”)

x

x

1017

1016

External control of auto/man function

Range:

0 = Off
1 = On

N.A.

(“E.Añ”)

x

x