TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS

“C.Cn.” - Menu Conf. 3 - CONTROL OUTPUT CONFIGURATION

ADDRESS

(Decimal)

DEC.

Display

R

W

R

Jbus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

2206

2205

Main control output conditioning

Range

0 = The control output is calculated by the
PID
1 = The control output is complemented
(100-PID calculated value)

N.A.

(“ñC.Cn”)

x

x

2207

2206

Main control output scaleable for display
in eng. unit

Range:

0 = Scaleable is not required
1 = Scaleable is required

N.A.

(“ñ.SCL”)

x

x

2208

2207

Decimal point position for main control
output display in eng. unit

Range:

0 = No decimal figure
1 = One decimal figure
2 = Two decimal figure

N.A.

(“ñC.dP”)

x

x

2209

2208

Low scale range value for main control
output display in eng. unit

See Mbus

word 301

or 2207

(“ñC.E.L.”)

x

x

2210

2209

High scale range value for main control
output display in eng. unit

See Mbus

word 301

or 2207

(“ñC.E.H.”)

x

x

2211

2210

Main control output auxiliary conditioning

Range:

0 = The functions described in the note
are applied “Before” of the “Main
control output conditioning” stage
1 = The functions described in the note
are applied “After” of the “Main control
output conditioning” stage

Note:

a - Control output limiter
b - Control output max rate of rise
c - Control output display value

N.A.

(“ñC.A.C.”)

x

x

2212

2211

Secondary control output conditioning

Note:

See “Main control output conditioning”

N.A.

(“SC.Cn.”)

x

x

2213

2212

Secondary control output scaleable for
display in eng. unit

Range:

0 = Scaleable is not required
1 = Scaleable is required

N.A.

(“S.SCL”)

x

x