Super Systems AC20 RS485 Modbus User Manual

Page 43

Advertising
background image

Page 43/59

TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS

“In.Ot.” - Menu conf. 5 - DIGITAL INPUT/OUTPUT CONFIGURATION

ADDRESS

(decimal)

DEC.

Display

R

W

R

JBus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

2401

2400

External contact “DIG1” function

Range:

0 = Input contact not used
1 = Input contact used for SP/SP2
auxiliary set point selection
2 = Input contact used for SP3/SP4
auxiliary set point selection
3 = Input contact used for Auto/Manual
selection
4 = Input contact used for output limiter
activation
5 = Input contact used to reset
(acknowledge) alarm

N.A.

(“d1.Fn”)

x

x

2402

2401

External contact “DIG1” logic level

Range:

0 = The input is at logic level “1” when
contact is open
1 = The input is at logic level “1” when
contact is closed

N.A.

(“d1.St”)

x

x

2403

2402

External contact “DIG2” function

Note:

See “External contact “DIG1” function”

N.A.

(“d2.Fn”)

x

x

2404

2403

External contact “DIG2” logic level

Note:

See “External contact “DIG1” logic level“

N.A.

(“d2.St”)

x

x

2406

2405

External contact “DIG3” logic level

Note:

See “External contact “DIG1” logic level“

N.A.

(“d3.St”)

x

x