7.4.2 Cut

off

A cut off flow rate can be programmed, that means, the flow rate below which the flow
rate indication will be zero. This can avoid reading errors in the lower zone of the scale.
The maximum allowed value for the cut off is the equivalent to a liquid velocity of 1 m/s.

7.4.3

Reversal flow rate

The MX4 is a bi-directional converter. The flow rate changes its sign automatically when
the flow is reversed. If after the converter has been installed it is necessary to reverse the
flow rate sign, in this screen it can be done by selecting the option “REVERSAL– Yes”.

7.4.4 Damping

El MX4 converter has an adaptive filter (damping) to provide stable flow rate and analog
output readings in the presence of continuous flow rate fluctuations.

The configuration of this filter can be very useful in the cases where the flow rate readings
have some instability (due to air bubbles, solids in suspension, etc.).

Only the flow rate indication of the display and the analog output are affected by the filter.
The relay output and the totalizer act according to the instant flow rate. Selecting a filter
with a longer or shorter integration time will provide more or less stable readings and will
also affect the response time to small variations of flow rate.

The integration time is selected in seconds, with a minimum value of 0 and a maximum
value of 40 seconds. For example, with an integration time of 15 seconds, the display will
indicate the flow rate reading of the average flow rate over the last 15 seconds from the last
update of the display. This does not mean that the display is refreshing its data every 15
seconds. The display shows a new value several times per second, indicating an average
of the flow rate values of the last 15 seconds.