Liquid line sizing, Discharge line sizing, 30 – 65°f leaving water temperature – AEC FSS Series 1.5- 10 HP Fountain Solution Systems User Manual

Page 34

Advertising
background image

FSS Series Fountain Solution Systems

Page 33

IAE-600

Liquid Line Sizing

The liquid line should be sized as small as possible, while
maintaining acceptable pressure drop, to minimize the refrigerant
charge. The total length between components must not exceed 200
actual feet or 300 equivalent feet. See Figure 11 for sizing.

Liquid risers should not exceed 15 feet.

Horizontal runs do not require a pitch. Insulation is not required
unless the line is installed in a high ambient area i.e. boiler room.

Install a liquid line charging valve to facilitate refrigerant charging.
Refer to Figures 13 and 14 for charge determination.

Discharge Line Sizing

For horizontal runs, the discharge line should be pitched
downward, in the direction of flow, at a rate of ½ inch for every 10
feet. This will allow oil to flow towards the condenser.

Discharge line sizing is based on the velocity required for
sufficient oil return back to the compressor. Discharge line sizing
is shown in Figure 12.

Figure 11

Liquid Line Sizing

30 – 65°F Leaving Water Temperature

Liquid Line Size (O.D.”)

Eqiv. FT

FSS-R-5

FSS-R-7.5

FSS-R-10

FSS-R-15

FSS-R-20

FSS-R-25

FSS-R-30

FSS-R-35

FSS-R-40

25

5/8

7/8

7/8

7/8

1 1/8

1 1/8

50

5/8

7/8

7/8

7/8

1 1/8

1 1/8

75

5/8

7/8

7/8

7/8

1 1/8

1 1/8

100

5/8

7/8

7/8

7/8

1 1/8

1 1/8

125

7/8

7/8

7/8

1 1/8

1 1/8

1 1/8

150

7/8

7/8

1 1/8

1 1/8

1 1/8

1 1/8

175

7/8

7/8

1 1/8

1 1/8

1 1/8

1 1/8

200

7/8

7/8

1 1/8

1 1/8

1 1/8

1 1/8

225

7/8

1 1/8

1 1/8

1 1/8

1 1/8

1 3/8

250

7/8

1 1/8

1 1/8

1 1/8

1 1/8

1 3/8

275

7/8

1 1/8

1 1/8

1 1/8

1 1/8

1 3/8

300

5/8

5/8

7/8

7/8

1 1/8

1 1/8

1 1/8

1 3/8

1 3/8