FSS Series Fountain Solution Systems

IAE-600

7-5 Graphic Panel Indicators and Switches

Compressor On Light (1.5 Ton Unit Only)

The

Compressor On

light turns on whenever the compressor is

operating.

Important!

Your AEC, Inc. warranty does not cover damage from evaporator freeze-up.

Be sure there is enough glycol in the system and that the High/Low thermostat

is set to the correct cutout temperature to prevent freeze-up!

Hot Gas By-Pass Light (1.5 Ton Unit Only)

The

Hot Gas By-Pass

light turns on when the hot gas bypass

valve is in operation. The

OUT1

LED

on the controller also lights

when the hot gas bypass valve is in operation.

Pump On Light

The

Pump On

light, installed on chillers with a pump, lights

whenever the pump(s) operates.

High Refrigerant Pressure Light (1.5 Ton Unit Only)

The

High Refrigerant Pressure

light comes on if the compressor

discharge pressure exceeds the limit of the high pressure cut-out
switch. The compressor stops but the pump(s) continue to run
until you manually reset the high pressure cut-out switch. Call a
qualified refrigeration service technician or contact the AEC
Service Department.

Low Refrigerant Pressure Light (1.5 Ton Unit Only)

The

Low Refrigerant Pressure

light comes on if the compressor

suction pressure drops below the limit of the low pressure cut-out
switch. The compressor shuts off, but the pump(s) continues to
run.

The indicator turns off and compressor restarts automatically when
the refrigerant pressure raises to the limit of the low pressure cut-
out switch. Call a qualified refrigeration service technician or
contact the AEC Service Department
.