Refrigerant charge determination, Oil charge determination, Figure 12 discharge line sizing – AEC FSS Series 1.5- 10 HP Fountain Solution Systems User Manual

Page 35: 30 – 65°f leaving water temperature

Advertising
background image

Page 34

FSS Series Fountain Solution Systems

IAE-600

Figure 12

Discharge Line Sizing

30 – 65°F Leaving Water Temperature

Discharge Line Size (O.D.”)

Eqiv. FT

FSS-R-5

FSS-R-7.5

FSS-R-10

FSS-R-15

FSS-R-20

FSS-R-25

FSS-R-30

FSS-R-35

FSS-R-40

25

7/8

1 1/8

1 3/8

1 3/8

1 5/8

1 5/8

1 5/8

50

7/8

1 1/8

1 3/8

1 3/8

1 5/8

1 5/8

1 5/8

75

7/8

1 1/8

1 3/8

1 3/8

1 5/8

1 5/8

1 5/8

100

7/8

1 1/8

1 3/8

1 3/8

1 5/8

1 5/8

1 5/8

125

7/8

1 1/8

1 3/8

1 3/8

1 5/8

1 5/8

2 1/8

150

7/8

1 1/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

175

1 1/8

1 1/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

200

1 1/8

1 3/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

225

1 1/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

2 1/8

250

1 1/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

2 1/8

275

1 1/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

2 1/8

300

1 1/8

1 1/8

1 3/8

1 5/8

1 5/8

2 1/8

2 1/8

2 1/8

2 1/8

Refrigerant Charge Determination

The approximate amount of refrigerant charge required by the
system varies based upon the total length of the refrigerant lines
and the size of the chiller. First refer to Figure 13 for the amount of
charge based upon the model number of the chiller. Then add that
to Figure 14, discharge and liquid line refrigerant charges, based
upon line size and installed length of each. The final operating
charge must be verified by running the system and checking the
liquid line sight glass.

Figure 13

Figure 14

FSR Chiller + Condenser Charge

Field Installed Piping Charge

Chiller

Model

Lbs. of

R-22

Pipe O.D.

Inches

Discharge

Line

c

R-22(Lbs.)

Liquid Line

c

R-22(Lbs.)

FSS-R5

5.9

1/2”

˘

7.2

FSS-R7.5

6.1

5/8”

˘

11.5

FSS-R10

10.8

7/8”

1.6

24.0

FSS-R15

12.6

1 1/8”

2.7

40.9

FSS-R20

21.2

1 3/8”

4.0

62.2

FSS-R25

24.2

1 5/8’

5.7

88.1

FSS-R30

40.2

2 1/8”

10.0

153.0

FSS-R35

41.2

2 5/8”

15.0

236.0

FSS-R40

50.2

c

Based on 100 feet of pipe, 100 ºF Liquid, 100 ºF Discharge

Oil Charge Determination

The FSS-R Series circulators are factory charged with the amount
of oil required without field-installed piping. Additional oil
required is dependent upon the amount of additional refrigerant
added.