4sequence of operation, 1 solution circuit, 2 refrigeration circuit – AEC FSS Series 1.5- 10 HP Fountain Solution Systems User Manual

Page 38

Advertising
background image

FSS Series Fountain Solution Systems

Page 37

IAE-600

4

Sequence of Operation

4-1 Solution Circuit

Cooling water

To Process

and

From Process

connections are

made at the hose barbs provided outside the unit. Warm solution
(water and chemical mixture) returns from the process and goes
into the reservoir tank. The coolant is then pumped through the
evaporator where it is cooled. The coolant flows to the process and
returns to repeat the cycle.

A process water bypass located between the supply line and
reservoir tank allows minimal flow through the unit during
intermittent fluctuating flow conditions. It is not intended to
provide continuous full bypass flow.

This minimal flow allows the temperature sensor to signal the
controller to shut down the compressor because of the drop in
process water temperature. Typically the flow switch shuts down
the chiller in this low flow condition.

4-2 Refrigeration Circuit

FSS Series circulators are available with air-, water-, or remote air-
cooled refrigerant condensing. The refrigeration cycles differ only
in the way the compressed gas is condensed to a liquid.

Liquid refrigerant from the condenser heat exchanger flowing in
the liquid line passes through a shutoff valve into a filter/dryer that
removes moisture and other contaminants. A refrigerant sight glass
is provided. The refrigerant then passes through the thermal
expansion valve which allows the refrigerant to expand (boil off),
and cool the fluid inside of the evaporator. The refrigerant gas
flows through the suction line back into the compressor.