Fan failure, Mpu failure – H3C Technologies H3C S9500E Series Switches User Manual

Page 81

Advertising
background image

71

Fan failure

Table 26 Fan LED description

LED Status

Description

RUN

Off

The fan tray has failed.

Steady on

The fan tray is operating properly.

ALM

Off

The fan tray is in normal state.

Steady on

The fan tray is faulty.

When the RUN LED is off or the ALM LED is on, the fan tray fails.
To troubleshoot the fan tray:

1.

If both LEDs are off, check the power supply to make sure it is working properly. For more
information, see "

Power supply failure

."

2.

Check for blockage of the air intake and exhaust vents on the chassis. If they are blocked, clean
them to keep the air flowing.

3.

Unplug the fan tray, and plug it in again to make sure it is seated properly.

4.

Plug a spare fan tray into the slot. If the spare fan tray can work properly, you can conclude that
the old fan tray has failed.

5.

If you fail to identify the cause, contact the local agents or technical support engineers for help.