Electrical Connection

SMA Solar Technology AG

24

WB5A_6A-IA-IEN114540

Installation Manual

5.2 Connection to the Power Distribution Grid (AC)

5.2.1 Conditions for AC Connection

Cable Design

The maximum cable lengths relative to the cable cross-section are shown in the following table.

Cable Requirements

Connection requirements of the grid operator
Always observe the connection requirements of your grid operator.

Cable cross-section

Maximum cable length

WB 5000A/WB 5000A-11

WB 6000A/WB 6000A-11

6 mm²

18 m

15 m

10 mm²

31 m

25 m

16 mm²

49 m

41 m

Reducing line losses by half
If three inverters with symmetrical feed-in are combined to form a three-phase system, the
neutral conductor is not subjected to any load, and the line losses are halved. This
reduction of line losses by 50% increases the maximum cable length by 100%.

Object

Description

Value

A

External diameter

12 mm ... 25 mm

B

Cable cross-section

6 mm² ... 16 mm²

C

Stripping length

approx. 16 mm