2 motor performance fine tuning, Parameters for tuning the drive, Motor performance fine tuning – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 125

Advertising
background image

5.2

Motor Performance Fine Tuning

This section offers helpful information for counteracting oscillation, hunting, or other faults

that occur while performing a trial run.

Note:

This section describes parameters that are commonly edited. Consult Yaskawa for more information on

detailed settings and fine-tuning the drive.

u

Parameters for Tuning the Drive

Table 5.1 Parameters for Tuning the Drive

Problem

Parameter

Corrective Action

Default

Value

Suggested

Setting

• Motor hunting and

oscillation at speeds

between 10 and 40

Hz

Hunting

Prevention Gain

(n1-02)

• If insufficient motor torque relative to the

size of the load causes hunting, reduce the

setting.

• When motor hunting and oscillation occur

with a light load, increase the setting.

• Lower this setting if hunting occurs when

using a motor with a relatively low

inductance, such as a high-frequency motor

or a motor with a larger frame size.

1.00

0.00 to 2.00

• Motor noise
• Motor hunting and

oscillation at speeds

up to 40 Hz

Carrier

Frequency

Selection

(C6-02)

• If the motor noise is too loud, increase the

carrier frequency.

• When motor hunting and oscillation occur

at speeds up to 40 Hz, lower the carrier

frequency.

• The default setting for the carrier frequency

depends on the drive capacity (o2-04) and

the Drive Duty Selection (C6-01).

7 (Swing

PWM)

1 to 7

• Poor motor torque at

speeds below 10 Hz

• Motor hunting and

oscillation

Torque

Compensation

Gain (C4-01)

• If motor torque is insufficient at speeds

below 10 Hz, increase the setting.

• If motor hunting and oscillation with a

relatively light load, decrease the setting.

1.00

0.50 to 1.50

• Poor motor torque at

low speeds

• Motor instability at

motor start

Mid Output

Voltage A

(E1-08)

Minimum

Output Voltage

(E1-10)

• If torque is insufficient at speeds below 10

Hz, increase the setting.

• If motor instability occurs at motor start,

decrease the setting.

Note: The recommended setting value is for

200 V class drives. Double this value when

using a 400 V class drive.

E1-08:

18.4 V

E1-10:

13.8 V

Initial value

±5 V

• Poor speed

precision

Slip

Compensation

Gain (C3-01)

• After setting the motor-rated current

(E2-01), motor-rated slip (E2-02) and motor

no-load current (E2-03), adjust the slip

compensation gain (C3-01).

-

0.5 to 1.5

Note:

Use slip compensation to improve speed precision. First make sure that the proper values have been set

for the motor rated current to E2-01, motor rated slip (E2-02), and motor no-load current (E2-03). Next,

adjust the slip compensation gain set to C3-01 so that it is between 0.5 to 1.5.