Terminal configuration, Output terminals, 7 control circuit wiring – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 54

Advertising
background image

n

Output Terminals

Table 3.7 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-Function

Digital Output

MA N.O. output (fault)

Digital output

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA (reference value)

MB N.C. output (fault)
MC Digital output common

Monitor Output

AM Analog monitor output

0 to 10 Vdc (2 mA or less) Resolution: 1/256

AC Monitor common

0 V

u

Terminal Configuration

S1

S2

S3

S4

S5

SC

A1 +V

AC AM AC

MC

MB

MA

Figure 3.11 Control Circuit Terminal

3.7 Control Circuit Wiring

54

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide