Digital Operator Display

Minor Fault Name

Phase loss in the drive input power. Check for wiring errors in the main circuit drive input power. Correct

the wiring.

YES

Loose wiring in the drive input

power terminals.

• Ensure the terminals have been properly tightened.
• Apply the tightening torque specified in this manual to fasten the

terminals.

Refer to Wire Gauges and Tightening Torques on page

46

.

There is a problem with the drive

input power voltage.

• Check the voltage.
• Lower the voltage of the drive input power so that it is within the

limits listed in the specifications.

Drive internal circuitry is worn.

• Check the maintenance time for the capacitors (U4-05).
• Replace the drive if U4-05 exceeds 90%.

The drive input power transformer

is not large enough and voltage

drops when the power is switched

on.

• Check for a tripped alarm when the magnetic contactor, line

breaker and leakage breaker are turned on.

• Check the capacity of the drive input power transformer.

Air inside the drive is too hot.

Check the temperature inside the drive.

The CHARGE indicator light is

broken or disconnected.

Replace the drive.

5.5 Alarm Detection

146