Digital Operator Display

Minor Fault Name

Surrounding temperature is too

high

• Check the surrounding temperature.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool surrounding area.
• Remove anything near drive that may cause extra heat.

YES

Internal cooling fan has stopped.

• Replace the cooling fan.
• After replacing the fan, reset the cooling fan maintenance

parameter to (o4-03 = “0”).

Airflow around the drive is

restricted.

• Provide proper installation space around the drive as indicated in

the manual.

Refer to on page 30

.

• Allow for the specified space and ensure that there is sufficient

circulation around the control panel.

• Check for dust or foreign materials clogging cooling fan.
• Clear debris caught in the fan that restricts air circulation.

Digital Operator Display

Minor Fault Name

oL3

Overtorque 1
Drive output current was greater than L6-02 for longer than the time set in L6-03.

Cause

Possible Solution

Minor

Fault

(H2- =

10)

Inappropriate parameter settings.

Check parameters L6-02 and L6-03.

YES

There is a fault on the machine side

(e.g., the machine is locked up).

• Check the status of the machine.
• Remove the cause of the fault.

Digital Operator Display

Minor Fault Name

ov

DC Bus Overvoltage
The DC bus voltage exceeded the trip point.

For 200 V class: approximately 410 V

For 400 V class: approximately 820 V (740 V when E1-01 < 400)

Cause

Possible Solution

Minor

Fault

(H2- =

10)

5.5 Alarm Detection

144

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide