E: motor parameters, B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 222

Advertising
background image

u

E: Motor Parameters

E parameters set V/f characteristics and motor-related data.

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

E1: V/f Pattern Characteristics

Use E1 parameters to set V/f characteristics for the motor.

E1-01

<1>

Input Voltage

Setting

This parameter must be set to the power supply

voltage.

WARNING! Drive input voltage (not motor voltage)

must be set in E1-01 for the protective features of the

drive to function properly. Failure to do so may result

in equipment damage and/or death or personal

injury.

155 to

255

230

S

300

101

E1-03 V/f Pattern

Selection

F: Custom V/f. E1-04 through E1-10 settings define

the V/f pattern.

F

F

O

302

E1-04 Maximum

Output

Frequency

E1-04, E1-06 to E1-10 can only be changed when

E1-03 is set to F.

To set linear V/f characteristics, set the same values

for E1-07 and E1-09. In this case, the setting for

E1-08 will be disregarded.

Ensure that the four frequencies are set according to

these rules to prevent triggering an oPE10 fault:

E1-09 ≤ E1-07 < E1-06 ≤ E1-04

E1-05

E1-08

E1-10

E1-09

E1-07 E1-06

E1-04

VACrms Out (V)

Frequency (Hz)

40.0 to

400.0

60

Hz

S

303

101

E1-05

<1>

Maximum

Output

Voltage

0.0 to

255.0

230

V

S

304

101

E1-06 Base

Frequency

0.0 to

E1-04

60

Hz

O

305

101

E1-07 Middle

Output

Frequency

0.0 to

E1-04

3.0

Hz

O

306

101

E1-08

<1>

Middle

Output

Frequency

Voltage

0.0 to

255.0

18.4

V

O

307

101

E1-09 Minimum

Output

Frequency

0.0 to

E1-04

1.5

Hz

S

308

101

E1-10

<1>

Minimum

Output

Frequency

Voltage

0.0 to

255.0

13.8

V

O

309

101

E2: Motor Parameters

Use E2 parameters to set motor-related data.

E2-01 Motor Rated

Current

Sets the motor nameplate full load current in

amperes.

Note: Set E2-03 (Motor No-Load Current) before

making changes to E2-01. Setting E2-01 < E2-03 will

trigger an oPE02 error.

10 to

200% of

drive

rated

current

<2>

S

30E

104

E2-02 Motor Rated

Slip

Sets the motor rated slip in Hertz.

0.00 to

20.00

<2>

O

30F

104

B.2 Parameter Table

222

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide