B.2 parameter table, A: initialization parameters – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 215

Advertising
background image

B.2

Parameter Table

An “O” in the “Mode” column indicates that the parameter is available in the Advanced menu.
An “S” in the “Mode” column indicates that the parameter is available in the Startup menu.

u

A: Initialization Parameters

The A parameter group creates the operating environment for the drive. This includes the

parameter Access Level, and Password.

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

A1: Initialization Parameters

Use A1 parameters to configure the basic environment for drive operation.

A1-01

<1>

Access Level

Selection

Selects which parameters are accessible via the

digital operator.

0: Operation only

2: Advanced Access Level

0, 2

2

O

101

117

A1-03 Initialize

Parameters

Resets all parameters to factory default settings.

(Initializes the drive then returns A1-03 to 0)

0: No Initialization

2220: 2-Wire Initialization

3330: 3-Wire Initialization

0 to

3330

0

O

103

88

E1-03, L8-35, o2-04, o2-09, and all U2

monitors are not reset when performing

initialization.

A1-04 Password

When the value set into A1-04 does not match the

value set into A1-05, parameters A1-01 and A1-03

cannot be changed.

0 to

9999

0

O

104

117

A1-05 Password

Setting

0 to

9999

0

O

105

117

This parameter is hidden from view. To

access A1-05, first display A1-04.

Then press the STOP key while holding

down the up arrow key. Parameter

A1-05 will appear.

<1>

Parameter can be changed during run.

B.2 Parameter Table

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

215

B

Parameter List

Advertising