Other functions of the fc 715 control unit – MCZ Boxsystem 75 FR User Manual

Page 33

Advertising
background image

Chapter 5

INSTALLATION AND USE MANUAL

page

33

Operation

Technical service – MCZ S.p.A. all rights reserved - Reproduction prohibited

The yellow buttons + and - can be used to increase/decrease the fan

speed from the 1

st

to the 4

th

speed and vice versa. The control unit

responds with a number of beeps corresponding to the selected speed:

1

st

Speed

= 1 long BEEP

2

nd

Speed

= 2 long BEEPS

3

rd

Speed

= 3 long BEEPS

4

th

Speed

= 4 long BEEPS

The switching on and off of the ventilation is determined exclusively by

the temperature of the thermostatic probe.

AUTOMATIC SWITCH-ON BY THE PROBE:
If the temperature detected by the probe is above 45°C, the fan

switches on at the set speed (1

st

speed) and an internal timer is

activated which begins to count down a period of 40 minutes. This 40-

minute period is called the “

heating phase".

After the 40-minute period has passed, if the temperature of the probe

is above 65°C, this means that the internal temperature is rising

because the insert is in full operation and consequently the fan must

remain on. If instead the 40-minute period has passed and the probe

has not reached 65°C, this means that fire operation is low and thus

the ventilation should switch off.
If the user changes the speed while the system is between 45°C to

65°C, this is interpreted as the desire to ventilate and thus the system

returns to the

heating phase , resetting the timer to 40 minutes and

starting the countdown.

AUTOMATIC SWITCH-OFF BY THE PROBE:
If the temperature probe drops below 65°C, the ventilation switches

off.

5.7.1.5. Other functions of the FC 715 control unit

STAND-BY: The fan is off because the blue ON/OFF button of

the radio remote control has been pressed. This shutdown is

signalled by one long beep.

SAFETY: In the STAND-BY state, if the temperature exceeds

the value of 150°C, the fan is activated at speed 1 and the

system goes into AUTOMATIC mode. The ventilation continues

until the temperature drops below 65°C.

STATUS RECOVERY: The system automatically stores the last

power set by the user in the non-volatile memory , allowing the

user to continue at this speed after a power failure.

5.7.1.6. Setting the transmission code of the radio

remote control

The radio remote control and the control unit are set with a neutral

code that immediately allows control of the ventilation kit operation

before completion of the cladding.
It may become necessary, however, to change this code and thus the

transmission frequency in the event another fireplace heating system is

present nearby (ex.: a neighbour has one) or if other signal

interference creates transmission problems.

BATTERY COMPARTMENT

AND SWITCH

ON

OFF

MAN

AUT