Operating via a web browser within your own network

There is also a

10% Diagnosis Function

to simulate a dynamic reduction to 10%.

The values are displayed in the table.

Note

!

The 10% Diagnosis Function can only be used when the 70% Fixed Reduction has

been activated.

Explanation of the Values in the Power Reduction Section

The following values are displayed in the Power Reduction section:

Power reduction type determined by:

The currently active control source is indicated in this field.

Displayed Text

Explanation

Text

PMC_NONE

No control source.

PMC_DIAG

Controlled by the diagnostic mode.

PMC_MODBUS_2

Controlled by the ModBus PM V2 (new ModBusPM).

PMC_MODBUS_1

Controlled by the ModBus PM V1 (old ModBusPM).

PMC_PROFILE

Controlled by the PM Profile.

PMC_INTERN

Controlled by the internal configuration.

PMC_DM_MODBUS

Controlled by direct seller via ModBusDM.

PMC_DM_RCR

Controlled by direct seller via ripple control receiver

Type of Reduction:

This contains the current type of power reduction that is specified by the control source.

Displayed Text

Explanation

Text

PMF_NONE

No power reduction function.

PMF_PR_ERROR

An error occurred while determining the power reduction func-
tion.

PMF_PR_FIX_PERC

Fixed reduction at % DC.

PMF_PR_FIX_KW

Fixed reduction at X kW (AC)

PMF_PR_VAR_PERC

Fixed reduction at % DC with self-consumption calculation.

PMF_PR_VAR_KW

Fixed reduction at X kW (AC) with self-consumption calculation.

PMF_PR_FIX_MATRIX

Reduction based on the value from the matrix (ripple control
receiver configuration).

PMF_PR_VAR_MATRIX

Reduction based on the value from the matrix (ripple control
receiver configuration) with self-consumption calculation.